7.1. Sprinkler
Pendent Type Sprinkler
The Globe GL-Series Residential Pendent Sprinklers have a low profile yet durable design, which utilize a 3mm frangible glass ampule as the thermosensitive element. They feature economy, pleasing aesthetics and low flow with K-Factors ranging from 3.0K to 5.6K
Technical Data
- Temperature Rating 68 Deg C
- Water Working Pressure Rating 12 bar
- Frame Material : Bronze
- Deflector Material : Brass
- “ K “ Factor 5.6 (80 metric)
- Thread Size ½” NPT
- Length 6.4 cm
Horizontal Sidewall Type Sprinkler
The Globe Model GL4231 and GL4431 Residential Horizontal Sidewall Sprinklers have a durable design, which utilizes a 3mm frangible, glass ampule as the thermosensitive element. They feature economy, pleasing aesthetics and a low flow with 4.2K and 4.4K factors.
Technical Data
- Temperature Rating 68 Deg C
- Water Working Pressure Rating 12 bar
- Frame Material : Bronze
- Deflector Material : Brass
- “ K “ Factor 4.2 (59 metric)
- Thread Size ½” NPT
- Length 6.4 cm
Upright Type Sprinkler
The Globe Model GL1167 Extra Large Orifice Upright Sprinkler is intended for use in NFPA 13, 231, 231C, 231D and 231F Systems, when installed in accordance with the Standard Sprinkler Positioning and area / density flow calculation requirements as specified in each respective standard.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
Temperature Rating – 155°F (68°C), 175°F (79°C),
200°F (93°C), 286°F (141°C).
Water Working Pressure Rating – 175 psi (12 Bars).
Minimum Operating Pressure – 10 psi (0.7 Bars).
Factory tested hydrostatically to 500 psi (34 Bars).
Maximum low temperature glass bulb rating is -67°F (-55°C).
Frame – bronze Deflector – brass Screw – brass
Bulb seat – copper Spring – nickel alloy Seal – teflon
Bulb – glass with glycerin solution, 5mm size.